multiple diesel fuel combustion chambers

The incinerators to be supplied shall meet the following specifications
1.ISO certified
2.Model:  multiple diesel fuel combustion chambers
3.Performance capacity 
120Kg/hr GRE 1.25 for HCRW
96Kg/hr GRE 1.25 for general waste.
40Kg/hr GRE 3.00 for plastic
4.Waste  type :   health care risk waste and general waste
5. Chimney stack:           
Chimney : 3.5mm mild steel
Height from base :11m and if there are buildings within
                                                30m of the incinerator, chimney must extend at least 3m
                                               above the apexes of all the roof of such buildings
Diameter of chimney at top :430mm
Weight of stack:  ±500 Kg
Case and stack be painted with 400⁰C heat resistant Black paint
6.Burners:
1st  chamber 850⁰C  – 900⁰C
2nd  chamber 1000⁰C
7.Variable speed combustion air blowers
8.Primary chamber volume  ±1.05 cubic metres
9.Mixing chamber volume  ±0.30 cubic metres
10.Settling chamber volume ±0.89 cubic metres
11.Weight excluding chimney  ±6.400Kg at manufacture
12..Firing tools supplied :Hoe ,poker and rake
13.Dimensions
Length                   ±2125mm
Width                    ±1890mm
Height                   ±2125mm
Extra width for burners ± 1000mm
14.Loading door opening 610 *540mm
15.Hearth area  ±1.19square metres
16.Description of grate/hearth :A full hearth to be supplied to prevent contaminated
17.Liquids from flowing into ash pit without being incinerated
18.Compliance with South African Atmospheric Pollution Prevention Act No.45 of 
1965 or equivalent air pollution standards
19.Documents to be supplied :Operations and maintenance manual and standard
operating procedures (SOPs)
        20. Emission controls:
heated refractory screen
Low velocity grit settling chamber
Stainless steel arrester screen